GC-RB01

BACnet BUILDING CONROLLERS

BACnet Integration Device - BACnet Ethernet Global Controller (Bacnet IP - MSTP)

GC-RB01 is Stand Alone controller (B-BC) with router function (no I/O). It can allow access between workstation and Bacnet MSTP controllers as well as providing a supervisory role to any other Bacnet device.

Description

GC-RB01 is Stand Alone controller (B-BC) with router function (no I/O). It can allow access between workstation and Bacnet MSTP controllers as well as providing a supervisory role to any other Bacnet device.

There is one 100M Bases-TX Ethernet port BACnet Ethernet or BACnet/IP and one BACnet MSTP port for Lan communications. Inbuilt standard programmable logic functions and BACnet object functions such as calendar, schedule, notification class, event enrollment, trend–logs etc.

GC-RB01 has programmable logic function and support standard BACnet object function such as calendar, schedule, notification class, event enrollment, trend–logs etc. GC-RB01 in conformity with international BACnet network communication and fully compatible with any BACnet system. It is absolutely the best product for your building.

Features

  • Conforms to BACnet MS/TP, BACnet Ethernet ISO-8802-2, BACnet/IP protocol. BTL approved.
  • Use 32-bit microprocessor, frequency 55MHz.
  • 128K RAM /512KB Flash, 32K FRAM for power failure memory.
  • B-BC level standard BACnet compliant controller plus network router function.
  • Ethernet communication interface can be either BACnet Ethernet(ISO-8802-2) or the BACnet/IP communication protocol.
  • MS/TP RS-485 communication interface, communication speed from 9.6 to 76.8 Kbps adjustable (Auto/Man), transmission distance 1,200 meters, up to 16 DAC or DSC controllers can be connected.
  • Each MS/TP port has 2500Vrms optical coupling isolator and TVS ARRAY surge protection.
  • RS-232 connection for initial device parameters (Using a Terminal program such as HyperTerminal).
  • On-line editing (does not affect other devices on the network), real-time program debugging function.
  • Operation functions of proportional, integration, differential, floating, logic, mathematic, enthalpy and dew point etc. Program executes cycle time 1 second.
  • Real-time clock, 2 Calendars, 20 Schedules, 4 Notification Class, 40 Event Enrollments, 24 Trend-logs, standard BACnet object.  Schedules and event enrollments support external object access.
  • Possessed 150 analog value (AV) points, 150 binary value (BV) points (BV points have 16 priority arrays).